Glazing Performance Calculator: U-Factor, R-Value, SHGC & VT

How well does a window’s glass insulate, how much solar heat does it let in, and how much daylight? Build a single, double, triple, or vacuum glazing unit pane by pane (clear or low-iron glass, low-e coatings on any surface, and air, argon, krypton, xenon, or vacuum gaps) and get its center-of-glass U-factor, solar heat gain coefficient (SHGC), and visible transmittance (VT), calculated the way NFRC rates them, with the matching R-value in US and SI units.

You also get reflectance, color, surface temperatures, and spectra. Use it to compare glazing options, see what a coating or a gas fill changes, convert between U-factor and R-value, or evaluate the measured spectra of a specific product.

Key terms
U-factor
The heat that flows through each square meter of glazing for each degree of temperature difference between inside and outside, in W/m²·K (US units: Btu/h·ft²·°F; 1 Btu/h·ft²·°F = 5.678 W/m²·K). Lower insulates better. The R-value, next, is the same property turned upside down.
R-value
The resistance of the glazing to heat flow: the U-factor turned upside down, so a higher R-value insulates better, and halving the U-factor doubles the R-value. US practice writes it as “R-4”, in h·ft²·°F/Btu. The SI value, in m²·K/W, is often called RSI and is about 5.7 times smaller. The R-values here are center-of-glass values from indoor air to outdoor air, so they include the thin layers of air on the two outer glass faces (the air films). The R-value printed on insulation is for the material alone, without air films, so the two are not directly comparable. A whole window, with its frame and edge, has a lower R-value than its center of glass.
Center of glass
The middle of the glazing, away from the edge seal and the frame. These results are center-of-glass values; the whole-window U-factor on an NFRC label also counts the frame and the edges and comes out higher, and the whole-window R-value lower.
SHGC
Solar heat gain coefficient: the fraction of the sunlight striking the glass that ends up as heat indoors, transmitted directly or absorbed in the panes and released inward. It runs from 0 to 1: low values keep rooms cool, high values help passive solar heating.
Visible transmittance (VT)
The fraction of daylight that passes through, weighted by the eye’s sensitivity. Clear double glazing transmits about 80 %.
Low-e coating
A thin, transparent coating of doped tin oxide or silver that reflects the long-wave infrared radiated by room-temperature surfaces. Its emissivity, from 0 to 1, says how strongly a surface radiates heat: 0.84 for bare glass, about 0.15 for a tin-oxide hard coat, and about 0.015–0.04 for silver coatings.
Surface numbers
Glass surfaces are counted from outdoors: a double unit has surfaces #1 (outdoor face) to #4 (indoor face), so a coating on #2 is on the inner face of the outer pane, inside the sealed gap.
Gas fill
Argon, krypton, or xenon conducts heat less well than air, so a filled gap insulates better. Here a gas fill is 90 % gas and 10 % air.
Vacuum insulating glass (VIG)
Two panes a fraction of a millimeter apart with the air pumped out, held apart by a grid of small pillars and sealed at the edges. Heat crosses only by radiation and through the pillars, so a VIG can insulate about as well as triple glazing in a unit under 1 cm thick, about a third of the thickness of a double-glazed unit.

Glazing system

Start from:

Height of the glass. It sets the convection in the gaps and on the indoor surface, so U and the R-value change slightly with it. LBNL WINDOW reports glazing systems at 1 m, the NFRC default; whole-window ratings use the product’s own height.

Performance

NFRC 100 / 200

Waiting for valid inputs.

Purple line: low-e coating. Orange: surface temperatures (°C) at NFRC 100 winter conditions, −18 °C outside and 21 °C inside.

Center of glass
—U-factor W/m²·K
—U-factor Btu/h·ft²·°F
—R-value h·ft²·°F/Btu
—R-value m²·K/W
—SHGC
—Visible transmittance

A lower U-factor is a higher R-value. Both run from indoor air to outdoor air, so they include the air films on the glass. For scale: about 5.8 W/m²·K (R-0.98, or 0.17 m²·K/W) for single glass, 2.7 (R-2.1, 0.37) for clear double glazing, 1.4 (R-4.1, 0.71) for low-e double glazing with argon, and 0.6–0.7 (R-9.5 to R-8.1, 1.7–1.4) for low-e triple glazing. The converter below turns any one of the four numbers into the other three.

Color as CIELAB under daylight (D65): L* is lightness from 0 (black) to 100 (white); negative a* is greener and positive a* redder; negative b* is bluer and positive b* yellower.

Visible reflectance, outside / inside—
Solar transmittance—
Solar reflectance, outside / inside—
Solar absorptance by pane— Pane 1 is the outdoor pane. Most of the heat absorbed in the outdoor pane flows back outside; most of the heat absorbed in the room-side pane flows indoors.
UV transmittance 310–380 nm—
Light-to-solar gain VT/SHGC— Daylight per unit of solar heat: about 1.1 for clear glass, typically 1.25–2 or more for spectrally selective low-e glazing.
R-value of the glazing alone without air films— The panes and gaps only, from the outdoor glass surface to the indoor one, at NFRC 100 winter temperatures. The center-of-glass R-value above adds the two air films. The R-value printed on insulation also leaves the air films out, so this is the nearer number to set beside it. It is still center of glass, and the frame and edge of a real window lower it.
Indoor glass temperature, winter—

U-factor and R-value converter

W/m²·K
Btu/h·ft²·°F
h·ft²·°F/Btu
m²·K/W

Starts at the calculator’s center-of-glass result. Type in any field to convert another value.

R-value is 1 divided by the U-factor, so a lower U-factor is a higher R-value. 1 Btu/h·ft²·°F = 5.678263 W/m²·K, so the US R-value is 5.678263 times the SI value (RSI). The arithmetic is the same for any U-factor or R-value you type. For this calculator’s result it gives a center-of-glass, air-to-air R-value, which includes the indoor and outdoor air films. The R-value printed on insulation is for the material alone, and a whole window, with its frame and edge, has a lower R-value than its center of glass.

R-value by layer, center of glass

NFRC 100 winter

The layers resist heat flow in series. Their resistances add up to the center-of-glass R-value, which is 1/U, and each takes a share of the 39 K between indoor and outdoor air in proportion to its resistance. The two surface rows are the air films that this R-value includes. Within a gap, radiation and the gas (or the pillars of a vacuum gap) carry heat side by side, so their coefficients add. R is given in m²·K/W (SI) and in h·ft²·°F/Btu (US units, 5.678263 times the SI number), ΔT in kelvin, and the coefficients in W/m²·K.

Spectral transmittance and reflectance

Shaded: the solar spectrum that weights the solar values, AM1.5 direct normal as NFRC 300 specifies (ISO 9845-1:1992, the ASTM E891 values). The visible band, 380–780 nm, is marked.

Use measured product data

Paste or load spectra for a specific product

Paste or load spectral data for a specific glass or coated product: a file exported from LBNL Optics in IGDB format, a product record (JSON) from LBNL’s IGSDB (sign-in required), or a manufacturer’s table. Each data row needs the wavelength, T, Rfront, and Rback, with wavelengths in µm or nm and values as fractions or percent; use a period as the decimal mark. The data should cover 300–2500 nm, and emissivities should be hemispherical, as in IGDB files. Imported products appear in the glass list for every pane, where you choose which way the product’s measured front face points. They stay in this browser and are not uploaded.

    How it is calculated

    The calculator works the way LBNL WINDOW does for a glazing system. It finds the spectral transmittance and reflectance of each pane, combines the panes optically, and then solves the heat balance of every glass surface under the NFRC conditions.

    Light and solar radiation

    Each pane is described by its spectral transmittance \(T(\lambda)\) and its front and back reflectance \(R_f(\lambda)\) and \(R_b(\lambda)\) from 300 to 2500 nm, in 5 nm steps. The panes are combined with the net-radiation (multiple-reflection) method, which follows light bouncing between every pair of surfaces. For two panes,

    \[ \begin{gathered} T = \frac{T_1 T_2}{1 - R_{b,1} R_{f,2}}, \\ R_f = R_{f,1} + \frac{T_1^2 R_{f,2}}{1 - R_{b,1} R_{f,2}}, \end{gathered} \]

    and the same bookkeeping gives the fraction of sunlight absorbed in each pane. The visible and solar values are weighted averages over the spectrum:

    \[ \begin{gathered} \tau_v = \frac{\sum D_{65}(\lambda)\,V(\lambda)\,T(\lambda)}{\sum D_{65}(\lambda)\,V(\lambda)}, \\ \tau_s = \frac{\sum E(\lambda)\,T(\lambda)}{\sum E(\lambda)} \end{gathered} \]

    Here \(D_{65}\) is the CIE daylight illuminant and \(V(\lambda)\) the eye’s daylight (photopic) sensitivity, summed over 380–780 nm. \(E(\lambda)\) is the AM1.5 direct-normal solar spectrum that NFRC 300 specifies (ISO 9845-1:1992, Table 1, column 2, the values of ASTM E891), summed over 300–2500 nm; about half of its energy is visible light. Reflectances are weighted the same way. The UV transmittance is the solar-weighted average from 310 to 380 nm, calculated the way LBNL WINDOW does it. Color is CIELAB under D65 with the CIE 1931 2° observer.

    Heat transfer, U-factor, and R-value

    The thermal model is the ISO 15099 center-of-glass method, which NFRC 100 prescribes and LBNL WINDOW implements. Every glass surface has its own temperature. The model solves the heat balance of all surfaces together and repeats it with updated, temperature-dependent coefficients until it converges.

    Double glazing, argon, low-e on #2OutdoorsIndoorsconvection 26radiation 3.2convection 2.4radiation 4.7radiation0.11gas1.72Gap: radiation + gas conductionand convection, side by side Vacuum glazing, low-e on #2OutdoorsIndoorsconvection 26radiation 3.2convection 2.1radiation 4.7Gap: radiation 0.18 +pillar conduction 0.80Edge seal (not in center-of-glass U)
    How heat crosses a glazing in winter, with the heat transfer coefficients the calculator finds for its default double glazing (left, drawn to scale) and for a vacuum glazing of two 4 mm panes with the single-silver coating on #2 and 0.5 mm pillars 25 mm apart (right, gap and pillars enlarged), in W/m²·K. In series, the layer with the smallest coefficient dominates: here the gap. The low-e coating cuts radiation across the gap to about a thirtieth of its value between bare glass surfaces, so gas conduction and convection, or the pillars of a vacuum glazing, carry most of the heat. The double glazing comes to U = 1.37 W/m²·K (R-4.16, or 0.732 m²·K/W) and the vacuum glazing to 0.83 W/m²·K (R-6.84, or 1.20 m²·K/W).

    The U-factor is the heat flow through the center of the glass, per unit area and per degree of difference between the indoor and outdoor air. The R-value is its inverse, and each has an SI and a US form:

    \[ \begin{gathered} R = \frac{1}{U}, \\ U_\text{US} = \frac{U_\text{SI}}{5.678263}, \qquad R_\text{US} = 5.678263\,R_\text{SI} \end{gathered} \]

    \(U_\text{SI}\) is in W/m²·K and \(R_\text{SI}\), often called RSI, in m²·K/W. \(U_\text{US}\) is in Btu/h·ft²·°F and \(R_\text{US}\) in h·ft²·°F/Btu, the number in “R-4”. The factor is 1 Btu/h·ft²·°F expressed in W/m²·K, and it follows from the definitions of the Btu (International Table), the foot, the hour, and the degree Fahrenheit. For the default unit, \(U = 1.366\) W/m²·K is 0.2405 Btu/h·ft²·°F, and \(R = 0.7321\) m²·K/W is R-4.157. The calculator converts the unrounded U-factor, so its four numbers always agree. Because this \(U\) runs from indoor air to outdoor air, \(1/U\) includes the resistance of the air films on the outdoor and indoor glass surfaces, the first and last terms of the sum in the equations below.

    Show the heat-transfer equations: gaps, glass surfaces, and vacuum glazing

    Across each gap, heat flows by radiation between the two facing surfaces,

    \[ h_r = \frac{\sigma\,(T_1^2 + T_2^2)(T_1 + T_2)}{1/\varepsilon_1 + 1/\varepsilon_2 - 1}, \]

    and by conduction and convection of the gas, \(h_c = \mathrm{Nu}\,k/d\), for a gap of width \(d\) and height \(H\). The Nusselt number Nu depends on the Rayleigh number of the gap:

    \[ \begin{gathered} \mathrm{Ra} = \frac{\rho^2 d^3 g\, c_p\, \Delta T}{\mu\, k\, T_m}, \\ \mathrm{Nu} = \max\!\left(\mathrm{Nu}_1,\ 0.242\left(\frac{\mathrm{Ra}\,d}{H}\right)^{0.272}\right) \end{gathered} \]

    \(\mathrm{Nu}_1\) is Wright’s (1996) correlation for vertical window cavities: \(0.0673838\,\mathrm{Ra}^{1/3}\) above \(\mathrm{Ra} = 5\times10^4\), \(0.028154\,\mathrm{Ra}^{0.4134}\) from \(10^4\) to \(5\times10^4\), and \(1 + 1.7596678\times10^{-10}\,\mathrm{Ra}^{2.2984755}\) below \(10^4\). The second term, from ElSherbiny, Raithby, and Hollands (1982), matters only in short cavities. At low Ra, Nu approaches 1: the gas only conducts, and \(h_c = k/d\). The gas properties vary linearly with temperature and are taken at the mean gap temperature \(T_m\). The 90 % fills contain 10 % air, mixed by the ISO 15099 rules (Wilke’s rule for viscosity, Mason and Saxena’s for thermal conductivity). Glass conducts with \(k = 1.0\) W/m·K.

    On the outdoor surface, wind convection is \(h_c = 4 + 4v = 26\) W/m²·K at the NFRC wind speed of 5.5 m/s, and the glass radiates to surroundings at the outdoor air temperature. On the indoor surface, natural convection follows the ISO 15099 correlation for a vertical plate as tall as the glazing, \(\mathrm{Nu}_H = 0.56\,\mathrm{Ra}_H^{1/4}\), with a turbulent branch above \(\mathrm{Ra}_H \approx 1.1\times10^{11}\) and air properties at \(T_i + (T_s - T_i)/4\). The glass also exchanges radiation with a room at the indoor air temperature. NFRC 100 sets the winter conditions: −18 °C outside with 5.5 m/s wind, 21 °C inside, and no sun. At the converged temperatures, the layers act as thermal resistances in series:

    \[ \frac{1}{U} = \frac{1}{h_o} + \sum_j \frac{t_j}{k_j} + \sum_k \frac{1}{h_{r,k} + h_{c,k}} + \frac{1}{h_i} \]

    Here \(h_o\) and \(h_i\) are the outdoor and indoor surface coefficients, convection plus radiation. The table under the results lists these resistances for your glazing. Their sum, \(1/U\), is the center-of-glass R-value in m²·K/W.

    Vacuum glazing

    A vacuum gap has no gas conduction or convection. Heat crosses it by radiation, with the same \(h_r\), and through the support pillars. Each pillar of radius \(a\) touches the glass on a small circle, and the heat it carries must spread out from that contact into each sheet: a spreading resistance of \(1/(4ka)\) per sheet (Collins et al., 1991). A square array of pillars with spacing \(\lambda\) therefore conducts

    \[ C_p = \frac{2\,k\,a}{\lambda^2} \]

    per unit area of glass with conductivity \(k\) (Collins and Fischer-Cripps, 1991). For example, 0.5 mm pillars 25 mm apart conduct 0.80 W/m²·K. The formula assumes pillars that conduct much better than glass, such as metal ones. A pillar of conductivity \(k_p\) and height \(h\) adds its own resistance, \(C_p = 2ka/[\lambda^2(1 + 2kh/(k_p \pi a))]\), as LBNL WINDOW models it. For a steel pillar 0.2 mm high and 0.5 mm across (\(k_p \approx 16\) W/m·K), that lowers \(C_p\) by about 3 %; for a glass pillar (\(k_p \approx 1\) W/m·K), by about a third.

    Residual gas is neglected. At 0.1 Pa the mean free path of air molecules, about 66 mm (see the mean free path calculator), is far larger than the gap, so the gas conducts as free molecules, \(C_g = \alpha\,\frac{\gamma + 1}{\gamma - 1}\sqrt{\frac{R}{8\pi M T}}\;p\) (Corruccini, 1959), where \(\alpha\) is the combined accommodation coefficient and \(\gamma\) the heat-capacity ratio. With the accommodation coefficients LBNL uses (0.5 at each surface), air at 0.1 Pa adds about 0.04 W/m²·K, ten times less at 0.01 Pa.

    Solar heat gain

    SHGC is the solar transmittance plus the fraction of the absorbed sunlight that flows inward. The calculator solves the heat balance twice under the NFRC 200 summer conditions: 32 °C outside with 2.75 m/s wind (so \(h_c = 15\) W/m²·K) and 24 °C inside. The first solution includes 783 W/m² of sunlight at normal incidence absorbed in the panes, the second has none, and the difference in heat flow into the room is the inward-flowing part:

    \[ \begin{aligned} \mathrm{SHGC} &= \tau_s + \frac{q_\text{in}(I_s) - q_\text{in}(0)}{I_s} \\ &= \tau_s + \sum_i N_i\,\alpha_{s,i} \end{aligned} \]

    Here \(\alpha_{s,i}\) is the solar absorptance of pane \(i\) and \(N_i\) its inward-flowing fraction. Each pane’s absorbed heat is split equally between its two surfaces. In the default unit, about 7 % of the heat absorbed in the outer pane flows inward, and 84 % of the heat absorbed in the inner pane.

    Generic glass and low-e coatings

    Generic panes use a soda-lime glass model: a refractive index near 1.52 and an absorption spectrum set by iron (Rubin, 1985). Ferrous iron (Fe²⁺) absorbs in a broad band centered near 1050 nm whose tail reaches into the red. That band cuts near-infrared transmission and gives clear glass its blue-green tint, plainest at the edge. Ferric iron (Fe³⁺) absorbs mainly in the ultraviolet (Shelby, 2015). Low-iron glass has less iron, more of it ferric. For 6 mm clear float, the model gives 89 % visible and 80 % solar transmittance, against 88 % and 77 % for LBNL’s generic 5.7 mm clear glass. For 6 mm low-iron glass it gives 91 % and 90 %, against 91 % and 89 % for the 5 mm low-iron glass of the EnergyPlus dataset.

    The four generic coatings stand for the main low-e families: a pyrolytic (hard-coat) doped tin oxide with an emissivity of 0.15, and sputtered single-, double-, and triple-silver stacks with emissivities of 0.04, 0.025, and 0.015. These, like all emissivities on this page, are hemispherical values as NFRC 301 defines them; a European “corrected emissivity” (EN 12898) runs 3–5 % lower for low-e coatings, and the low-e coating calculator gives both from a sheet resistance. LBNL’s documentation gives about 0.15 as typical of hard coats (0.1 or less for newer ones), 0.04 of sputtered coatings, and 0.02 for the best available. More silver layers make a steeper rise in near-infrared reflectance, so less solar heat passes for the same daylight. The emissivity of the coated surface sets the radiation across the gap. Real products vary, so use measured spectra for a specific product. If you know only the emissivity of your coating, enter it in the optional Emissivity field of the coated pane: it replaces the generic value in the heat-transfer calculation, while the spectra stay those of the chosen family.

    Surface numbering. Surfaces are numbered from the outside: a double unit has surfaces #1 (outdoor face) to #4 (indoor face). Moving a coating from #2 to #3 leaves the U-factor and the R-value unchanged but raises SHGC, because the sunlight the coating absorbs then heats the inner pane, whose heat flows mostly indoors. For the default double-silver unit, SHGC is 0.37 with the coating on #2 and 0.42 on #3. So #3 is the usual choice where solar gain is welcome, and #2 where it is not.

    Typical values

    Center-of-glass results of this calculator for common glazings, with generic layers under NFRC conditions, 1 m tall. Double units have 6 mm panes and a 12.7 mm gap. The R-value is 1/U, from indoor air to outdoor air, so it includes the air films. The “Start from” buttons above the glazing form load four of these rows: clear double with air, the default, the triple with krypton, and the vacuum glazing with pillars 25 mm apart.

    GlazingU, W/m²·K
    (Btu/h·ft²·°F)
    R, h·ft²·°F/Btu
    (m²·K/W)
    SHGCVT
    Single, 6 mm clear5.81 (1.02)0.98 (0.17)0.8489 %
    Double, clear, air2.68 (0.47)2.12 (0.37)0.7380 %
    Double, hard coat on #3, argon1.63 (0.29)3.48 (0.61)0.6975 %
    Double, single silver on #2, argon1.40 (0.25)4.06 (0.71)0.5573 %
    Double, double silver on #2, argon (the default)1.37 (0.24)4.16 (0.73)0.3774 %
    Triple, 4 mm panes, single silver on #2 and #5, 12 mm argon0.73 (0.13)7.82 (1.38)0.4762 %
    Triple, 4 mm panes, double silver on #2 and #5, 12 mm krypton0.60 (0.11)9.43 (1.66)0.3263 %
    Vacuum, 4 mm panes, single silver on #2, 0.5 mm pillars 25 mm apart0.83 (0.15)6.84 (1.20)0.5774 %
    The same with pillars 40 mm apart0.45 (0.08)12.50 (2.20)0.5774 %

    Typical inputs: uncoated glass has an emissivity of 0.84; LBNL gives about 0.15 for pyrolytic and 0.04 for sputtered silver coatings, and 0.02 for the best. Under NFRC winter conditions, U is lowest, and the R-value highest, with gaps of about 12 mm for air or argon, 8 mm for krypton, and 6 mm for xenon; wider gaps convect more. Vacuum glazings have gaps of 0.1–0.2 mm, evacuated below 0.1 Pa, with pillars about 0.25–0.5 mm across and 2–5 cm apart (Simko et al., 1995; Curcija and Hart, 2018).

    Worked example

    The default unit: two 6 mm clear panes, the double-silver coating (ε = 0.025) on #2, and a 12.7 mm gap of 90 % argon, 1 m tall. Under NFRC 100 winter conditions the surfaces settle at −16.2, −15.9, 13.1, and 13.5 °C (#1 to #4).

    In total, \(R = 0.0342 + 0.0060 + 0.5445 + 0.0060 + 0.1414 = 0.7321\) m²·K/W. That sum is the center-of-glass R-value in SI units. In US units it is \(5.678263 \times 0.7321 = 4.157\) h·ft²·°F/Btu, shown as R-4.16. The U-factor is its inverse: \(U = 1/0.7321 = 1.366\) W/m²·K, shown as 1.37 (0.241 Btu/h·ft²·°F). The gap holds 74 % of the resistance and takes 29 K of the 39 K difference. The two air films, \(R_o\) and \(R_i\), hold 24 %; without them, the panes and the gap alone come to 0.5565 m²·K/W (R-3.16). Under NFRC 200 summer conditions, τs = 0.333, and the panes absorb 27.6 % and 2.1 % of the sunlight. Their inward-flowing heat adds 0.035, so SHGC = 0.368. VT is 73.8 %, and VT/SHGC = 2.0.

    Assumptions and limits

    References

    Primary sources and standards

    1. ISO 15099:2003, Thermal performance of windows, doors and shading devices — Detailed calculations, 1st ed., confirmed in 2026 (the center-of-glass thermal model: surface heat balances, linear gas properties and mixing rules, the cavity and indoor convection correlations, and SHGC).
    2. ANSI/NFRC 100-2026 [E0A1], Procedure for Determining Fenestration Product U-factors, National Fenestration Rating Council (2026), §4.3.1, nfrc.org (the winter conditions, the 26.00 W/m²·K outdoor film, indoor convection from the product height, and the requirement to model vacuum insulating glass).
    3. ANSI/NFRC 200-2026 [E0A0], Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence, NFRC (2026), §4.3.1 (the summer conditions and 783 W/m² of sun for center-of-glazing SHGC).
    4. NFRC 300-2026 [E0A0], Test Method for Determining the Solar Optical Properties of Glazing Materials and Systems, NFRC (2026), §7.2 (the solar spectrum of ISO 9845-1:1992, Table 1, column 2; D65 with the 1931 color-matching function ȳ = V(λ); linear interpolation; trapezoidal integration).
    5. NFRC 301-2026 [E0A0], Standard Test Method for Emittance of Glazing Products, NFRC (2026), §9, Eq. 9-3 (hemispherical emissivity of coated glazing from its normal emissivity at 300 K, after Rubin, Arasteh, and Hartmann) and §6.4 (0.84 for uncoated float glass).
    6. ISO 9845-1:1992, Solar energy — Reference solar spectral irradiance at the ground at different receiving conditions — Part 1: Direct normal and hemispherical solar irradiance for air mass 1,5, withdrawn in 2022 (replaced by ISO 9845-1:2022) but still the spectrum NFRC 300 specifies; its direct-normal column holds the values of ASTM E891-87, used here as tabulated in LBNL’s Windows-CalcEngine.
    7. ASTM G173-23, Standard Tables for Reference Solar Spectral Irradiances: Direct Normal and Hemispherical on 37° Tilted Surface, ASTM International (2023), store.astm.org (the current reference spectrum, used for the comparison under Assumptions and limits).
    8. CIE 015:2018, Colorimetry, 4th ed., doi:10.25039/TR.015.2018, with the CIE datasets for illuminant D65 (doi:10.25039/CIE.DS.hjfjmt59), the photopic luminous efficiency V(λ) (doi:10.25039/CIE.DS.dktna2s3), and the 1931 2° color-matching functions (doi:10.25039/CIE.DS.xvudnb9b) (the visible weighting and CIELAB).
    9. J. L. Wright, “A correlation to quantify convective heat transfer between vertical window glazings,” ASHRAE Trans. 102(1), 940–946 (1996), hdl:10012/11574 (the vertical-cavity Nusselt correlation, fitted to data for aspect ratios above 40 and Ra up to 10⁶).
    10. S. M. ElSherbiny, G. D. Raithby, and K. G. T. Hollands, “Heat transfer by natural convection across vertical and inclined air layers,” J. Heat Transfer 104, 96–102 (1982), doi:10.1115/1.3245075 (the aspect-ratio term 0.242(Ra/A)0.272).
    11. C. R. Wilke, “A viscosity equation for gas mixtures,” J. Chem. Phys. 18, 517–519 (1950), doi:10.1063/1.1747673, and E. A. Mason and S. C. Saxena, “Approximate formula for the thermal conductivity of gas mixtures,” Phys. Fluids 1, 361–369 (1958), doi:10.1063/1.1724352 (the mixing rules ISO 15099 adopts).
    12. D. C. Curcija, S. Vidanovic, R. Hart, J. Jonsson, R. Powles, and R. Mitchell, WINDOW Technical Documentation, Lawrence Berkeley National Laboratory (2018), windows.lbl.gov (§5.1.2.3, the ISO 15099 boundary conditions, cavity correlations, and gas mixtures as WINDOW implements them; §9, vacuum glazing, with typical emissivities and pillar geometry).
    13. D. C. Curcija and R. G. Hart, “Modeling thermal performance of VIG: WINDOW and THERM software tools,” 1st China (Qingdao) International Glass & Equipment Technology Seminar, LBNL (August 2018), windows.lbl.gov (the pillar-array and low-pressure gas formulas in WINDOW, pillar spacings of 2–5 cm, and center-of-glass versus whole-window U-factors).
    14. LBNL, WINDOW 8.1 User Manual (October 2026), windows-downloads.lbl.gov (§20.2: glazing-system U-factors at a 1 m height, the NFRC default; §8.2: the default optical standard, with ASTM E891 as the source spectrum and UV transmittance from 310 to 380 nm).
    15. R. E. Collins and T. M. Simko, “Current status of the science and technology of vacuum glazing,” Solar Energy 62, 189–213 (1998), doi:10.1016/S0038-092X(98)00007-3 (a review of vacuum glazing: heat flow by radiation, pillars, and the edge).
    16. R. E. Collins, L. Poladian, B. A. Pailthorpe, and R. C. McPhedran, “Heat conduction through support pillars in evacuated windows,” Aust. J. Phys. 44, 73–86 (1991), doi:10.1071/PH910073 (heat flow through a short circular contact between two sheets: the spreading resistance).
    17. R. E. Collins and A. C. Fischer-Cripps, “Design of support pillar arrays in flat evacuated windows,” Aust. J. Phys. 44, 545–564 (1991), doi:10.1071/PH910545 (the conductance of a pillar array and its trade-off with glass stress).
    18. T. M. Simko, R. E. Collins, F. A. Beck, and D. Arasteh, “Edge conduction in vacuum glazing,” in Thermal Performance of the Exterior Envelopes of Buildings VI (Clearwater Beach, FL, December 1995), ASHRAE (1996), pp. 601–611; LBL-36958, doi:10.2172/211577 (gaps of 0.1–0.2 mm, evacuation below 0.1 Pa, the solder-glass edge seal, and measured edge temperatures).
    19. J. Peng, Y. Tan, Y. Fang, H. Yang, A. Song, C. Curcija, and S. Selkowitz, “Excellent insulation vacuum glazing for low-carbon buildings: fabrication, modeling, and evaluation,” Engineering 53, 18–39 (2025), doi:10.1016/j.eng.2024.11.027 (an open-access review: pillar-array design trade-offs, pressure below 0.1 Pa, and edge effects).
    20. R. J. Corruccini, “Gaseous heat conduction at low pressures and temperatures,” Vacuum 7–8, 19–29 (1959), doi:10.1016/0042-207X(59)90766-3 (free-molecular gas conduction between parallel surfaces).
    21. M. Rubin, “Optical properties of soda lime silica glasses,” Solar Energy Materials 12, 275–288 (1985), doi:10.1016/0165-1633(85)90052-8; free preprint LBL-13572 at escholarship.org (optical constants of clear and low-iron glass, and the role of FeO and Fe2O3).
    22. EN 673:2024, Glass in building — Determination of thermal transmittance (U value) — Calculation method, CEN (2024), replacing EN 673:2011 (European Ug; vacuum glazing excluded, referred to EN 674 or ISO 19916-1). ISO 9050:2026, Glass in building — Determination of light transmittance, solar direct transmittance, total solar energy transmittance, ultraviolet transmittance and related glazing factors, replacing ISO 9050:2003 (excludes vacuum glazing). EN 410:2011, Glass in building — Determination of luminous and solar characteristics of glazing. EN 12898:2019, Glass in building — Determination of the emissivity (the European corrected emissivity). ISO 19916-1:2018, Glass in building — Vacuum insulating glass — Part 1.
    23. ISO 13837:2008 (withdrawn; replaced by ISO 13837:2021), Road vehicles — Safety glazing materials — Method for the determination of solar transmittance, §4.2, law.resource.org (ISO 9050:2003 and EN 410:2011 weight solar quantities with the air-mass-1 global spectrum of CIE 85, Table 4).
    24. O. A. Alduchov and R. E. Eskridge, “Improved Magnus form approximation of saturation vapor pressure,” J. Appl. Meteorol. 35, 601–609 (1996), doi:10.1175/1520-0450(1996)035<0601:IMFAOS>2.0.CO;2 (the Magnus form for the dew point; they recommend a = 17.625 and b = 243.04 °C, and the page uses Sonntag’s 17.62 and 243.12 °C, as in WMO-No. 8, which differ from them by about 0.01 °C here), checked against IAPWS R7-97(2012), iapws.org.
    25. LBNL, pyWinCalc and Windows-CalcEngine (BSD license), github.com/LBNL-ETA/pyWinCalc (used to check this calculator), and the EnergyPlus window glass dataset, WindowGlassMaterials.idf (generic clear and low-iron glass).

    Textbooks

    Free introductions